SPX Waukesha High Voltage Transformers
KVA Rating 156/208/260 MVA
Indeck Specials
- High Voltage Transformers HV138000 LV15600
- Baghouse (for Coal Fired Boiler to 380,000pph)
- Stock Boilers (to 250,000pph)
- Call Brian Dailey Direct (847) 541-8300 x3587 or Email
Type
- LT GSU
KVA Rating
- 156/208/260 MVA
Class
- OA/FA/FA
Temp Rise
- 55/60 (C)
HV
- 138000 GRDY/79670 WYE
Taps
- 131100, 134550, 138000,141450,144900
LV
- 15600 DELTA
MFG
- Waukesha
Radiators, Fan Assembly, Lapp POC and POC-A Condenser Bushings, Ohio Brass Dynavar VN Station Class Surge Arresters, Buchholz Relays
- Stored Indoors – Climate Controlled Building
- Nitrogen Blanket
Dimensions
- 260″ Height
- 165″ Width
- 188″ Length
Weight: (Approx. lbs.)
- Untanking – 192,000
- Tanks and Fittings – 90,000
- Oil (main tank) 11,370 gal – 86,400
- Oil (conservator) 600 gal – 4,600
- Total Weight – 373,000
Available Drawings
- Nameplate Drawing
- Schematic Diagram
- Transformer Outline
- O & M Manuals